Effect of Neutral Grounding Methods on the Earth Fault Characteristics
By
Proceedings of 2015 Photonics & Electromagnetics Research Symposium, Prague, July 6 - 9,Page(s)1144-1151
Abstract
Medium voltage (MV) distribution systems use different methods for grounding the neutral point. Influences of these grounding methods on the single line to ground (SLG) fault characteristics are discussed in this paper. Jordanian MV network is used as a case study. The network has both underground cables and overhead lines. Simulation models are implemented in both MATLAB/SIMULINK, and DigSilent/Power Factor software. The models allow de- tailed investigation of the different fault factors and grounding methods. Results are obtained to evaluate the impact of each grounding method on the SLG fault features. Isolated neutral, solid grounding, resistance grounding and Petersen coil (Arc suppression coil) grounding are compared for different fault locations, fault incidence angles, and fault resistances. Current and voltage waveforms, as well as symmetrical components are used to describe the fault case.
Citation
Abdallah R. Al-Zyoud, Abdullah Alwadie, Abdallah Basheer, and A. Elmitwally, "Effect of Neutral Grounding Methods on the Earth Fault Characteristics," Proceedings of 2015 Photonics & Electromagnetics Research Symposium, Prague, July 6 - 9,Page(s)1144-1151
References

1. Muhammad, T. A.-H., "Neutral ground resistor monitoring schemes," IEEE International Symposium on Electrical Insulation, Indianapolis, USA, 2004.        Google Scholar

2. Roberts, J., H. J. Altuve, and D. Hou, "Review of ground fault protection methods for grounded, ungrounded, and compensated distribution systems," Schweitzer Engineering Laboratories, 2001.        Google Scholar

3. Welfonder, T. and V. Leitloff, "Location strategies and evaluation of detection algorithms for earth faults in compensated MV distribution systems," IEEE Transactions on Power Delivery, Vol. 15, No. 4, 2000.
doi:10.1109/61.891492        Google Scholar

4. Griffel, D., Y. Harmand, V. Leitloff, and J. Bergeal, "A new deal for safety and quality on MV networks," IEEE Transactions on Power Delivery, Vol. 12, No. 4, 1428-1433, 1997.
doi:10.1109/61.634156        Google Scholar

5. Abdel-Fattah, M., "A transient fault detection technique with varying fault detection window of earth modes in unearthed MV systems," 6th International Conference on Power Quality and Supply Reliability, Estonia, 2008.
doi:10.1109/pq.2008.4653758        Google Scholar

6. Statan, I., I. Proouc, and I. Dobrea, "Contributions to the rational method of neutral grounding with MATLAB/SIMULINK," Technical University of Moldova, 2007.        Google Scholar

7. Gross, E. T. B., "Sensitive fault protection for transmission lines and distribution feeders," AIEE Transactions, Vol. 60, 968-972, 1941.        Google Scholar

8. Hunt, L. F. and J. H. Vivian, "Sensitive ground protection for radial distribution feeders," AIEE Transactions, Vol. 59, 84-90, 1940.
doi:10.1109/t-aiee.1940.5058102        Google Scholar

9. Zamora, I., A. J. Mazon, F. Antepara, M. Puhringer, and J. R. Saenz, "Experiences of neutral resonant system implementation in Gorliz substation," CI RED 17th International Conference on Electricity Distribution, 12-15, Barcelona, 2003.        Google Scholar

10. Van de Sandt, R., J. Lowen, J. Paetzold, and I. Erlich, "Neutral grounding in off-shore wind farm grids," IEEE Bucharest Power Tech. Conference, Romania, 2009.        Google Scholar

11. Dumitru Toader, S. H., C. Blaj, and I. Cata, "Numerical simulation of single phase faults in medium voltage electrical networks," University of Timisoara, Romania, 2010.        Google Scholar

12. Gernot Druml, A. K. and O. Seifert, "A new directional transient relay for high ohmic earth faults," CI RED 17th International Conference on Electricity Distribution, Barcelona, May 2003.        Google Scholar

13. Henriksen, T. and A. Petteteig, "Detection of earth fault in a medium voltage distribution network," International Conference on Power System Transients, Lyon, France, 2007.        Google Scholar

14. Cerretti, A., F. M. Gatta, A. Geri, S. Lauria, M. Maccioni, and G. Valtorta, "Temporary overvoltages due to ground faults in MV networks," IEEE PowerTech 2009, 1-8, Bucharest, 2009.
doi:10.1109/ptc.2009.5282140        Google Scholar

15. Mariappan, V., A. B. S. M. Rayees, and M. Al Dahmi, "Grounding system analysis to improve protection system performance in distribution networks," 12th IET International Conference on Developments in Power System Protection (DPSP 2014), 1-6, 2014.        Google Scholar

16. Toman, P., J. Dvořák, J. Orságová, and S. Mišák, "Experimental analysis of electrical values during earth faults," Electric Power Quality and Supply Reliability Conference (PQ), 185-190, 2010.
doi:10.1109/pq.2010.5550000        Google Scholar

17. Matti Lehtoneen, S., "Characteristics of earth faults in electrical distribution networks with high impedance grounding," Electric Power Systems Research, Vol. 44, No. 3, 155-161, 1998.        Google Scholar